Considered a process steam consumption operating under on/off conditions.
During normal operation (on) presents a corrosion rate of 2 mpy and produces
dissolved iron as corrosion result of 0.05 ppm.
If operation turns to off, steam is condenced, pressure drops, and oxygen
enters to the system as to brake the void.
Corrosion rate increases extremelly, and when system turns again to on
extremelly high iron return is noticed.
During the off operation the deterioration of the system is very fast.