Control Tests
In order to minimise scaling and/or corrosion of
these systems, the following control tests must be performed, and all water test
results must be documented on a dedicated record sheet (see typical record sheet
overleaf):
(a) Log the quantity of water
softened/dealkalised between regenerations;
(b) Log the make-up water meter reading at least
once per month;
(c) At least once per day on large systems and 3
times per week on small systems, perform the following tests on boiler water
samples and log these test results:
(i) neutralised total dissolved solids.... must
be 1500-3000 ppm (2000-4000 micromhos/cm);
(ii) phosphate ......................must be
40-80 ppm PO4;
(iii) hydroxide alkalinity.........must be
150-300 ppm CaCO3;
(iv) total alkalinity .................must be
less than 700 ppm CaCO3;
(v) sulphite...........................must be
30-60 ppm SO3; (50 ppm Na2 SO3)
(vi) pH ..............................must be
10.5-11.5.
(d) At least once per day on large systems and 3
times per week on small systems, determine and log the pH level of the
condensate return—it must be 8.5-9.5 pH for systems that are not used for
humidity control and 8.0-8.5 pH for systems that are used for humidity control;
(e) At least once per day on large systems and 3
times per week on small systems, determine and log the TDS concentration of the
condensate return—it must be less than 40 ppm (50 micromhos/cm);
(f) At least once per day on large systems and 3
times per week on small systems, determine and log the total hardness
concentration of the condensate return & softener effluent—they both must be
less than 2 ppm CaCO3;
(g) While performing the above tests, note the
general appearance of the water samples—the boiler water samples may be
colourless or amber & contain either no sediment or a small amount of sediment,
whereas the condensate & softener samples must be clear & colourless with no
sediment.
|