food grade product line by Water Services Ltd

AT 1123
Home Up

 

Home
Up


Deposit and corrosion inhibitor


liquid PHOSPHATE blend FOR BOILER SCALE CONTROL

 

DESCRIPTION:

AT 1123  is a liquid blend of selected poly-phosphates which react to precipitate calcium hardness in the boiler as a sludge and prevent formation of hard calcium carbonate, sulfate and/or silicate scale.

The finely-divided, non-adherent calcium phosphate sludge remains suspended in the boiler water until removed via the blowdown.

AT 1123 contains the best and most highly concentrated phosphates to assure maximum results with a minimum of treatment.

 

Features

AT 1123 contains phosphate sequestrants, polymers and antifoam. The phosphate is used to prevent calcium hardness depositing on the heat transfer surfaces. The sequestrants are used to form soluble heat stable complexes with constituents which act as binders for normal water sludge.

The synthetic polymers prevent suspended solids of any kind from adhering to internal boiler surfaces and will gradually remove existing deposits. The antifoam helps preventing boiler water carry over.

 

ADVANTAGES:

·         Prevents calcium scale deposits.

·         Forms nonadherent sludge.

·         Cost-effective. A phosphate precipitation program can be the most economical where significant hardness levels exist in the feedwater.

·         Clear and easy dosage control.

 

DOSAGES:

AT 1123 dosages depend upon many factors including the chemical characteristics of the makeup water, boiler operations, percentage of condensate return, etc. Approximate requirements can be estimated as ¾ pound of treatment per pound of calcium hardness entering the boiler. Individual dosage recommendations are made for each installation by your Water Services Ltd representative, based on his survey. Dosage is controlled by a simple color comparison test.

 

FEEDING:

AT 1123 is compatible with most boiler water chemicals and can be blended with them in the treatment feed tank

The dosage of AT 1123 is adjusted to maintain an excess of phosphate in the boiler water.

AT 1123 may be fed directly from the drum. The preferred feedpoint is to the steam drum through the chemical feedline, although feeding to the preboiler system is also acceptable.

Specific recommendations will be made by your Water Services Ltd representative for each installation.


Handling precautions

Wear suitable gloves and safety goggles. In case of contact immediately flush with water.

After eye contact seek medical advice. In case of spillage, absorb with sand or other absorbent materials and sweep up. Then flush the area with water.

After exposures to temperatures below 10°C, re-heat product and mix thoroughly.

Before use review the Material Safety Data Sheet for additional information.

 

Transport classifications

A.D.R. : not classified

IMDG : not classified

U.N.nr. : not classified

Labelling for handling

Symbol : not regulated

R-phrases : none

S-phrases : none

 

PACKAGING

AT 1123 is packaged in 35 Kg PE drums.

 

REGULATORY STA  TUS:

AT 1123 complies with FDA regulations for boiler water additives used in the preparation of steam that will contact food, and is authorized by USDA for use in federally inspected meat and poultry plants.

.


All statements, information and data presented herein are believed to be accurate and reliable but are not to be taken as a guarantee, express warranty or implied warranty of merchantability of fitness for a particular purpose, or representation, express or implied, for which seller assumes legal responsibility, and they are offered solely for your consideration, investigation and verification. Statements or  suggestions concerning possible use of this product are made without representation or warranty that any such use is free of patent infringement and are not recommendations to infringe any patent

 

Home Up